AWS EC2/EBS us-east-1: traffic shifted onto low-capacity redundant network
During a change to upgrade capacity on the primary EBS network in one Availability Zone, traffic was shifted off a primary router incorrectly. Instead of going to the other primary router it went onto the lower-capacity redundant EBS network, isolating many EBS nodes; when connectivity returned a re-mirroring storm left 13% of volumes in the AZ stuck. Full recovery took about 3 days.
A reconstruction, not the operator's network. Hammerhead's authors rebuilt the change from the public record as a small network of their own. No configuration here is the operator's. What follows is what the tool reported on that reconstruction; it is not a claim that the tool would have prevented the outage.
What happened
Who: Amazon Web Services
The summary at the top is paraphrased from the sources below. Hammerhead's catalog rates its confidence in this account high.
Sources
What the public record says
- During a change to upgrade capacity on the primary EBS network in one Availability Zone, traffic was shifted off a primary router incorrectly. Instead of going to the other primary router it went onto the lower-capacity redundant EBS network, isolating many EBS nodes; when connectivity returned a re-mirroring storm left 13% of volumes in the AZ stuck. Full recovery took about 3 days.
- Who: Amazon Web Services
What the reconstruction assumed
Decided by Hammerhead's authors to build a network that runs. None of it describes the operator's network.
Everything below is ours.
- Same shape as GCE 2015, and the same template: the redundant lower-capacity network is a router attached at a high IGP cost, and the traffic shift takes both primary routers out of the path instead of one.
- Cisco IOS syntax and stand-in address space throughout. A reconstruction, not any operator's configuration.
What Hammerhead said
Each run below is pinned by Hammerhead's replay tests at commit 0ee9732: the verdict and the quoted text are checked against the tool's output, and a run that disagrees fails the test. Reason lines are copied verbatim; a pinned line can be part of a longer reason. Every preflight run uses --max-blast-radius 100, so a change is never counted as caught merely because it touched many devices of a small network.
Hammerhead's own first-versus-now record
- First verdict
- pass.
- Verdict now
- fail: SECONDARY-NET-1 carries nothing today and would carry everything. The re-mirroring storm that followed is application behaviour and out of remit.
Quoted from docs/replays/families/individual.md. “First” is the tool before the fixes this replay prompted.
as intended: one production router drained onto the other
now: passOn the reconstruction, hammerhead preflight on a before and an after snapshot returned pass.
Pinned in tests/gauntlet/replays-individual.yaml.
as done: traffic moved off both
now: failOn the reconstruction, hammerhead preflight on a before and an after snapshot returned fail, for the reasons below.
Reason text pinned (some reason contains each line)
- path change: SECONDARY-NET-1 carries no traffic between other devices today and would carry it
Pinned in tests/gauntlet/replays-individual.yaml.
What changed in Hammerhead because of it
From the “What was fixed” table in Hammerhead's replay notes, where each fix landed after a failing test. “Found by” is copied as written; a family name means the batch this incident belongs to.
A router drawn into the path
The AS-level path check is blind inside one AS. A device present in both snapshots, in the middle of no path today and of some path after, is named. Every ECMP branch is walked, because the single-path walker follows one member and the others are not idle (the Azure drain caught the first version of this).
Found by: GCE 2015, AWS EBS 2011, T-Mobile
Limits
- The configurations are a reconstruction. Where the record is silent, the assumptions above fill the gap; if one is wrong, the replay is wrong in that respect.
- A verdict describes the reconstructed network's converged state. Timing, traffic load, and anything a device does that no configuration states, such as software reacting to a health check or a firmware bug, are outside it.
- A pass is reported as a pass. A fail says a gate fired on the reconstruction, nothing more.
- Why the catalog counts this outage as in scope: A pre-push simulation of the traffic shift shows EBS traffic converging on a network that cannot carry it; this is the textbook 'shifted onto a path that cannot carry it' case.
Not fixed: Load, and what a router is built to carry
No config says. The finding is that traffic moves onto a router that carries nothing today; whether it can is the operator's to confirm. With capacity and demand declared (--link-capacity), the capacity rows fail on load for T-Mobile, GCE 2015 and Cloudflare 2020, with illustrative figures, since no public record gives them. Load under a link failure, queueing and router CPU are still not modelled.
Recorded against: GCE 2015, AWS EBS 2011, T-Mobile, Google Cloud Aug 2016
Imported from docs/replays/aws-ebs-2011/FACTS.md and the replay manifests in the Hammerhead repository at commit 0ee9732.